Understanding the 1785-BCM
Hardware Components

Chapter 2

2-4

Table 2.A
Communication Ports

Communication Port:

This link is used to:

High Speed Serial Link (HSSL)

permit two-way alternating communication (half-duplex)
between the two 1785-BCM modules of the backup system
at a distance of up to 15 feet.

Channel 1A

connect the primary PLC-5 processor to the Data Highway
Plus network or to the remote I/O link; the secondary
processor is isolated from this link.

Channel 1B

connect the primary PLC-5 processor to the Data Highway
Plus network or to the remote I/O link; the secondary
processor is isolated from this link.

Channels 1A and 1B have a default communication mode which can be
changed by resetting switches, if necessary. Table 2.B describes the default
communication mode for each of the two channels.

Table 2.B
Default Communication Modes

Channel

Default Communication Mode

1A

Data Highway Plus

1B

Remote I/O – Scanner mode at 57.6 kbaud

With the exception of the HSSL, all of the connections in the 1785-BCM
module have an internal relay whose contacts are closed when the
controller is primary and open when the processor is secondary. Figure 2.3
shows these relays for processor A and processor B of a PLC-5 backup
system.