background image

Installing Your PLC-5 Backup System

Chapter 3

3-9

Table 3.F
Configuring 1785-BCM Series B Channels 1A and 1B using SW2

Configure Channel 1A switches

1

Configure Channel 1B switches

2

for:

1

4

2

5

3

6

Data Highway Plus network at 57.6 kbaud (refer to Chapter 5, section
“Secondary Processor Remote Programming”)

ON

ON

ON

Remote I/O – adapter mode using 57.6 kbaud

ON

ON

OFF

Remote I/O – adapter mode using 115.2 kbaud

ON

OFF

ON

Remote I/O – adapter mode using 230.4 kbaud

ON

OFF

OFF

Relay switching or unused Channel

3

OFF

ON

ON

Remote I/O – scanner mode with 57.6 kbaud

OFF

ON

OFF

Remote I/O – scanner mode with 115.2 kbaud

OFF

OFF

ON

Remote I/O – scanner mode with 230.4 kbaud

OFF

OFF

OFF

1

Switches 1, 2, and 3 determine configuration for Channel 1A.

2

Switches 4, 5, and 6 determine configuration for Channel 1B.

3

Does not function as a smart switch but as a relay with contacts either opened or closed. Also, set

the switches in this configuration if you are not going to use this channel.

Important: The positions of the switches are read at the module power-up.
If the position of the switches is changed after module power-up, the
1785-BCM module does not recognize the new position.

Inserting the 1785-BCM Module into the I/O Chassis

To insert the 1785-BCM module in your I/O chassis, perform the following
steps. We recommend that you insert your 1785-BCM module into the
left-most slot of the first I/O module group in the I/O chassis.

ATTENTION: Remove power from the 1771 I/O chassis
backplane and wiring arm before removing or installing an I/O
module.

Failure to remove power from the backplane or wiring arm

could cause module damage, degradation of performance, or
injury.

Failure to remove power from the backplane could cause injury

or equipment damage due to possible unexpected operation.