Data table considerations – Rockwell Automation 1785-BCM_BEM, D17856.5.4 PLC-5 Backup Communication Module User Manual User Manual

Page 94

Advertising
background image

Switchover Considerations

Chapter 6

6-9

Several of the data table sections in the PLC-5 processor are not structured
with single 16-bit words. You need to consider this when applying the
1785-BCM module.

For example, the BTW of the primary processor transfers 62 words of data
to the secondary processor (plus the packet length and block ID word).
Some structures such as timers, counters, and floating point control files
have three words. If all related words don’t fit in a block, some words may
be truncated, creating a partial structure in the secondary processor
(Figure 6.2).

Figure 6.2
Partial Structure in BTW

BTW (64 words)

To secondary

Packet Length

Block ID

Words 3 – 62

.
.
.

Word 1

Word 2

Accumulated value is truncated

Word 63

Word 64

Preset value

Counter

Control Word

Word 65

11107I

Problem structures include:

timer

values

counter

values

floating point elements
control

registers

Data Table Considerations

Advertising