Diagnosing faults chapter 8 – Rockwell Automation 1785-BCM_BEM, D17856.5.4 PLC-5 Backup Communication Module User Manual User Manual

Page 113

Advertising
background image

= on

= off

= blinking

LEGEND:

Diagnosing Faults

Chapter 8

8-3

Table 8.C
BPLN, SER, and FLT LED Indicators

If this LED

is:

Description

Recommended Action

BPLN

SER

FLT

normal operation

no action required

BPLN

SER

FLT

PLC-5 processor is in PROGRAM mode
(normal operation)

block-transfer instruction fault; no block-transfer has
been requested

communication fault between the 1785-BCM
module and the I/O chassis such as: short in the
I/O chassis connector

Check that the PLC-5 is in RUN mode.
Check the program.
Also check to see that the module is properly
inserted in the I/O chassis.
Check the backplane error bit (1 is local,
9 is remote) of the system status word.

If the fault persists, replace the 1785-BCM module
and check the backplane error bit (1 is local, 9 is
remote). If, again the fault persists, a problem may
exist with the I/O chassis backplane. If this is the
case, contact your local Allen-Bradley sales
representative.

BPLN

SER

FLT

High Speed Serial Link (HSSL) fault

Check the HSSL connectors on the 1785-BCM
module’s wiring arm; check the 1770-CD cable
making the HSSL connection also.
Check the serial communication error bit (0 is local,
8 is remote). If the error persists, replace the
1785-BCM module.

BPLN

SER

FLT

or

or

internal module hardware failure such as: watchdog
fault, checksum error, closing of a relay contact, etc.

Cycle power to the I/O chassis; if the failure
condition persists, replace the 1785-BCM module.

BPLN

SER

FLT

1785-BCM module is not receiving power

Turn off the power. Remove and reinstall the
module in the I/O chassis. Restore power.