Chapter

5

5-1

Operating Your PLC-5 Backup System

In this chapter we describe how the primary system transfers data to the
secondary system. We do this by describing the operation of the:

1785-BCM

module

PLC-5 backup system

In addition, we provide procedures for:

starting your system
powering up your system
disconnecting a faulted system
restarting a repaired system
changing the processor’s operating mode
editing a program on-line

In a PLC-5 backup system, the 1785-BCM module performs three distinct
functions:

automatic transfer of remote input data over the High-Speed

Serial Link (HSSL)

transfer of data in the data table by block-transfer instructions
secondary processor remote programming capability

Automatic Transfer of Remote Input Data Over the HSSL

With automatic transfer, the primary 1785-BCM module is continually updating
a copy of the remote input image table in an interface located in the secondary
1785-BCM module. This remote input data includes discrete data as well as
block-transferred data. Automatic transfer is carried out over the High Speed
Serial Link (HSSL) and is independent of the application program.

The secondary 1785-BCM module responds with current data to the remote I/O
scan requests of the secondary processor, making the secondary processor
“think” that it is communicating with remote I/O chassis. This response
prevents remote I/O faults in the secondary processor, since the secondary
processor is not physically connected to the remote I/O link (Figure 5.1).