Environment and enclosure – Rockwell Automation 1788-CN2FFR EtherNet/IP and ControlNet to FOUNDATION Fieldbus Linking Device User Manual

Page 11

Advertising
background image

Rockwell Automation Publication 1788-UM057B-EN-P - September 2014

9

Preface

Environment and Enclosure

European Hazardous Location Approval

ATTENTION: Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2 industrial

environment, in overvoltage Category II applications (as defined in IEC 60664-
1), at altitudes up to 2000 m (6562 ft) without derating.

This equipment is not intended for use in residential environments and may

not provide adequate protection to radio communication services in such
environments.

This equipment is supplied as open-type equipment. It must be mounted

within an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The enclosure must have
suitable flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA or be approved for the application
if nonmetallic. The interior of the enclosure must be accessible only by the use
of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.

In addition to this publication, see the following:

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1,

for additional installation requirements.

NEMA Standard 250 and IEC 60529, as applicable, for explanations of the

degrees of protection provided by enclosures.

ATTENTION: Do not place the module in direct sunlight. Prolonged exposure to
direct sunlight could degrade the LCD.