Rockwell Automation 1788-CN2FFR EtherNet/IP and ControlNet to FOUNDATION Fieldbus Linking Device User Manual

Page 78

Advertising
background image

76

Rockwell Automation Publication 1788-UM057B-EN-P - September 2014

Appendix C

Field Device Block Configuration Examples

18.

Verify that the MODE_BLK > TARGET value is Cas + Auto and the
MODE_BLK > ACTUAL value is Auto.

19.

In the parameter screen, scroll down to parameters CAS_IN and
BKCAL_OUT.

20.

Verify that the BKCAL_OUT > STATUS in the Live column indicates a
NotInvited condition.

Before the output control loop can be initialized, the NotInvited
condition must be cleared.