Field Device Block Configuration Examples

Appendix C

21.

Set the value of the controller tag that is associated with the quality of
CAS_IN (connector PV:O.1) status parameter (PVx_GoodCascade) to
the value 1.

22.

Verify that the NotInvited status has been replaced by the new status,
InitializationRequest.

The InitializationRequested must receive a response.

23.

Set the value of the Controller Tag associated with the substatus of
CAS_IN (connector PV:O.1) status parameter (PV1_SubStatus) to the
value 1, which is InitializationAcknowledge.