H1 master page, Field device page – Rockwell Automation 1788-CN2FFR EtherNet/IP and ControlNet to FOUNDATION Fieldbus Linking Device User Manual

Page 64

Advertising
background image

62

Rockwell Automation Publication 1788-UM057B-EN-P - September 2014

Appendix A

Linking Device Display Status

H1 Master Page

The next page that is accessed by the
Page button is the H1 Master page.

Bus A/B:

Displays the bus voltages,

currents, and bus status.

Temperature:

Displays the internal

temperature of the linking device.

External Pwr:

Displays the power

supply voltage.

FF Node:

Displays the H1 node

address for the master (default 16).

BusA/B Enabled:

H1 Bus A or H1 Bus B is enabled for communication.

BusA/B Tripped:

H1 Bus A or H1 Bus B has tripped indicating that there was

an over-current on either port.

BusA/B Term:

The linking device is configured to terminate H1 Bus A or H1

Bus B.

Field Device Page

The next 16 FF Field Device pages
display the status of each of the field
device indices.

FF Node:

Displays the H1 node

address.

Device Tag Name:

The tag name of

the device.

Status:

Displays the field device status

(see

Table 9

.)

Table 9 - Field Device Status

Success:

Displays the data packets that are received as a percentage of packets

that are sent for the previous 100 packets.

Pckt Send:

Displays the total number of data packets that are sent from the field

device.

Status

Description

Not Connected

Device cannot be seen

Online

Online - not configured

ConfigRunning

Device is configured and
running