Appendix C
Field Device Block Configuration Examples
13.
Set the value of the Controller Tag associated with the substatus of
CAS_IN_D (connector PV:O.1) status parameter (PV1_SubStatus) to
the value 1, which is InitializationAcknowledge.
14.
Verify that the DO function block MODE_BLK > ACTUAL > Live
column displays Cas.
The DO function block is now created, initialized, and operating correctly.