Rockwell Automation Publication 1788-UM057B-EN-P - September 2014

31

Set Up in the Studio 5000 Logix Designer Application

Chapter 2

Figure 2 - Master Advanced Configuration Screen

Auto MacroCycle

Click the Auto MacroCycle button on the master configuration page to calculate
the recommended MacroCycle for the current linking device (see

Master

Configuration on page 28

).

Auto MacroCycle Calculation

Macrocycle = [(time for request + receive) x (configured field devices) x
(configured PVs for each field device)] + [(configured field devices) x (time for
one token exchange)] + [fixed amount of unscheduled time].

Add and Manage Device Description Files

Before field devices can be added to the 1788-CN2FFR/1788-EN2FFR linking
device, add a copy of the DD file to the field device catalog by using the
HSProcessUtility as described in

Appendix B

.

The DD file defines the capabilities and configuration parameters of the field
device.

IMPORTANT

The Auto MacroCycle only takes effect after you download it to the master and
field devices.