Linking Device Display Status

The display of the linking device provides status and diagnostic data in one of
three page formats: main page, H1 master page, or field device page. Use the
display Page button behind the front cover to scroll through the pages (see

Figure 8 on page 46

for location of the Page button).

Main Page

The main page is the default display, and
the linking device returns to this page after
10 seconds.

H1Bus A/B:

Displays the bus voltages on

each port.

IP:

Displays the current IP address or

BOOTP if enabled.

STS:

Displays the status (see

Table 7

).

Table 7 - STS Status Descriptions

The lower portion of the main page shows the communication quality to each
field device as the percentage of data packets sent compared to data packets
received for each field device index (see

Table 8

).

Table 8 - Field Device Communication Quality

Status

Description

Ok

No events

New device found

New device on the bus

Redundancy ok

Masters are synchronized

Redundancy err

Masters out of sync

Bus A Tripped

Bus A over current trip

Bus B Tripped

Bus B over current trip

SAFE MODE

linking device set to Safe mode

Display

Communication Quality

Display

Communication Quality

>>>

95+

???

Unknown

>>

80+

OOS

Allocated, On-line, not Compelling Data

>

60+

Off

Allocated, Off-line

XXX

Below 60

Err

Allocated, On-line, not producing
Compelled Data