Rockwell Automation Publication 1788-UM057B-EN-P - September 2014

23

Set Up in the Studio 5000 Logix Designer Application

Chapter 2

4.

Set the RPI for the linking device.

5.

Click OK to add the linking device to the I/O tree.

RSNetWorx for ControlNet Configuration

See the RSNetWorx for ControlNet Getting Results Guide, publication

CNET-

GR001

, for more details.

Follow these steps to configure the ControlNet network.

1.

Launch RSNetWorx™ for ControlNet and create a file.

2.

Click the Online button.

The Browse for Network window appears with the drivers you have
installed on your system.

IMPORTANT

The recommended RPI is 1/2 the macrocycle time. Calculate the macrocycle by
calculating the total response time of all field devices on the segment and then
add 100

200 ms for class 2 (DTM message) data. If the RPI is too low, class 1

data (PVs and status) does not update each cycle, and class 2 data responses
can be slow.