Rockwell Automation Publication 1788-UM057B-EN-P - September 2014

43

Set Up in the Studio 5000 Logix Designer Application

Chapter 2

Scheduling and the LAS

The 1788-CN2FFR/1788-EN2FFR linking device generates the LAS schedule,
which determines when each function block executes and transmits data. Newly
added field devices are automatically added to the schedule, and removed from
the schedule when removed from the live list.

Figure 7 - Master Configuration Dialog Box

The Download Schedule function is only needed when the 1788-CN2FFR/
1788-EN2FFR linking device has been replaced.

Redundant Master Setup

You can configure a second 1788-CN2FFR/1788-EN2FFR linking device to act
as a backup. You can choose from various architectures (see

Appendix D

). The

figure shows an example of MultiMaster architecture, A bus only, with a shared
termination.

IMPORTANT

When connecting to running linking devices, you must follow the procedures
in

MultiMaster Connecting Procedures on page 46

to avoid losing the

connection to certain devices.

IMPORTANT

You must not have any other back-up LAS devices. Be sure that the field devices
have been configured with the class set to basic. See

Field Device Class on

page 42

.

IMPORTANT

Test and verify that the specific field devices that are connected to the
MultiMaster operate correctly when one of the linking devices fails.