Rockwell Automation Publication 1788-UM057B-EN-P - September 2014
79
Field Device Block Configuration Examples
Appendix C
24.
Verify that the AO function block MODE_BLK > ACTUAL > Live
column displays Cas.
25.
Set the CAS_IN (PV:O.1) value to 50%.
26.
Verify that the BKCAL_OUT (PV:I.1) and OUT (PV:I.2) values change
as required (50% equals 12 mA at the OUT parameter).
The AO function block is now created, initialized, and operating correctly.