56

Rockwell Automation Publication 1788-UM057B-EN-P - September 2014

Chapter 4

Diagnostics

The count of good quality reply packets that are received from the field device.
(Cyclic Redundant Code [CRC] check passed.)

Bad CRC Packets

The count of reply packets that are received from the field device that were
rejected because the CRC check failed.

No Replies

The count of communication request to which the field device did not respond.

Success Rate

The rate of good replies to the number of requests for the last 100 requests.

Signal Quality

Displays the quality of the waveform for the field device by evaluating slew rate,
amplitude, distortion, noise, and balance.

Allocated

True if the field device has been allocated a field device index of 00 through 15.
If a field device is in the visitor list, it has not been allocated.

Compel

True if the field device has been allocated and configured to compel data.
The field device is also included in the schedule.

Live Data

True if the field device is allocated and configured, and is currently producing
live data.

Value

Description

0…33

Bad

34…66

Poor

67…100

Good