Rockwell Automation 1788-CN2FFR EtherNet/IP and ControlNet to FOUNDATION Fieldbus Linking Device User Manual
Page 56
Advertising

54
Rockwell Automation Publication 1788-UM057B-EN-P - September 2014
Chapter 3
Logix Assemblies
PVBinary1…PVBinary8
For a field device that requires an output, the data must be updated in the output
image of that field device. If the data type for the connector is set to Boolean,
then the data for that connector is read from the binary value in the output
image.
PVStatus1…PVStatus8
If the connector for the PV output is set to have a status, you must put a status in
the output image that will be sent with the process variable.
Figure 10 - Example of Field Device Output Screen
PV Status
Status
PVStatus
≥ 0x80
Green = good
0x40
≤ PVStatus < 0x80
Orange = uncertain
PVStatus < 0x40
Red = bad