H1 network connections – Rockwell Automation 1788-CN2FFR EtherNet/IP and ControlNet to FOUNDATION Fieldbus Linking Device User Manual

Page 16

Advertising
background image

14

Rockwell Automation Publication 1788-UM057B-EN-P - September 2014

Chapter 1

Installation

We recommend a 24

32V DC power supply for the linking device to operate

correctly. No additional power supplies or power conditioners are required. The
power supply connection is described here. Tighten DC Power connections to a
torque of 0.22…0.25Nm (2…2.2 lb-in).

H1 Network Connections

The H1 network must be connected via the H1
terminal on the linking device. The H1 network
connection and pinout is described here.

Make Fieldbus connections to a torque of
0.5…0.6 Nm (4.4…5.3 lb-in)

The H1 Segment is split between two physical
ports, A and B.

IMPORTANT

Do not use additional power supplies or power conditioners with the
1788-EN2FFR and 1788-CN2FFR linking devices.

Pin

Description

Right/Top (red)

FF +

Middle (green)

FF -

Left/Bottom

Shield