7-16

ControlLogix w/1769-ADN DeviceNet Ladder Example Program

ControlLogix w/1769-ADN Example Program

Figure 7.21 ControlLogix Ladder Logic Main Program

ControlLogixLogix DeviceNet w/ 1769-SM1 DPI/SCANport Module example program

The ControlLogix system contains a 1756-DNB (node 00). The 1769-SM1 is a component in a 1769-ADN DeviceNet adapter
drop (node 2) along with a 1769-PA4 power supply and 1769-ECR End Cap Terminator. The 1769-SM1 has a PowerFlex 70
connected to each of the three channels.

This rung commands the 1756-DNB to run.

0

Local:1:O.CommandRegister.Run

ControlLogixLogix DeviceNet w/ 1769-SM1 DPI/SCANport Module example program

The ControlLogix system contains a 1756-DNB (node 00). The 1769-SM1 is a component in a 1769-ADN DeviceNet adapter
drop (node 2) along with a 1769-PA4 power supply and 1769-ECR End Cap Terminator. The 1769-SM1 has a PowerFlex 70
connected to each of the three channels.

This rung commands the 1756-DNB to run.

Read the 2 words (4 bytes) of ADN overhead along with the entire input image (60 words) of the SM1.

1

Copy File
Source

Local:1:I.Data[0]

Dest SM1_Input_Data[0]
Length

62

COP

1769-ADN

Word 1

Read the 2 words (4 bytes) of ADN overhead along with the entire input image (60 words) of the SM1.

Execute the 1769-SM1 Channel 1 subroutine.

2

Jump To Subroutine
Routine Name Channel_1

JSR

Execute the 1769-SM1 Channel 1 subroutine.

Execute the 1769-SM1 Channel 2 subroutine.

3

Jump To Subroutine
Routine Name Channel_2

JSR

Execute the 1769-SM1 Channel 2 subroutine.

Execute the 1769-SM1 Channel 3 subroutine.

4

Jump To Subroutine
Routine Name Channel_3

JSR

Execute the 1769-SM1 Channel 3 subroutine.

Write the entire output image (60 words) of the SM1 to the DNB. Note the DNB is using DWords so the length is 30.

5

Copy File
Source SM1_Output_Data[0]
Dest

Local:1:O.Data[0]

Length

30

COP

Write the entire output image (60 words) of the SM1 to the DNB. Note the DNB is using DWords so the length is 30.

(End)