Powerflex 700s drives – Rockwell Automation 1769-SM1 Compact I/O to DPI/SCANport Module User Manual
Page 159
 
Logic Command/Status Words
E-3
Logic Command Word
PowerFlex 700S Drives
Logic Bits
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0 Command
Description
x Normal
Stop
0 = Not Normal Stop
1 = Normal Stop
x
Start
(1)
0 = Not Start
1 = Start
x
Jog 1
0 = Not Jog using [Jog Speed 1]
1 = Jog using [Jog Speed 1]
x
Clear 
Fault 
(2)
0 = Not Clear Fault
1 = Clear Fault
x
x
Unipolar 
Direction
00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Direction Control
x
Reserved
x
Jog 2
0 = Not Jog using [Jog Speed 2]
1 = Jog using [Jog Speed 2]
x
Current 
Limit Stop
0 = Not Current Limit Stop
1 = Current Limit Stop
x
Coast Stop 0 = Not Coast to Stop
1 = Coast to Stop
x
Reserved
x
Reserved
x
Spd Ref 
Sel0 
(3)
000 = Spd Ref A
001 = Spd Ref B
010 = Preset 2
011 = Ref. 3 (Preset 3)
100 = Ref. 4 (Preset 4)
101 = Ref. 5 (Preset 5)
110 = Ref. 6 (Preset 6)
111 = Ref. 7 (Preset 7)
x
Spd Ref 
Sel1 
(3)
x
Spd Ref 
Sel2 
(3)
x
Reserved
(1)
A “Not Stop” condition (logic bit 0 = 0, logic bit 8 = 0, and logic bit 9 = 0) must first be present before a “1 = Start” condition 
will start the drive.
(2)
To perform this command, the value must switch from “0” to “1.”
(3)
This command is available only for PowerFlex 700S drives with Phase II Control. For drives with Phase I Control, Logic 
Command bits 12, 13, and 14 are reserved.