Understanding the I/O Image

4-3

A Channel Enable Word is used for each channel (output words 0, 4, and
8), where:

The Channel Enable Word is a “master” enable/disable switch for
communications on each channel. The actual output/input data being
sent/received is determined by Parameter 07 - [I/O Config 1],
Parameter 24 - [I/O Config 2] and Parameter 41 - [I/O Config 3].

Important: If the Channel Enable bit is transitioned from ON (“1”) to

OFF (“0”), the connected drive product will fault.

A Channel Status Word is used for each channel (input words 0, 4, and
8), where:

Channel Enable Words

Bit #

Name

Description

0

Channel Enable

“0” = Disables sending output data (Logic Command/

Reference and Datalinks) to the channel. All input
data is zeroed (“0”) to indicate that the data is no
longer being updated.

“1” = Enables sending output data (Logic Command/

Reference and Datalinks) to the channel. All
respective input data will also be updated.

1-15

Not used

Reserved for future use

Channel Status Words

Bit #

Name

Description

0

Logic Status Valid

“0” = Logic Status/Feedback data is not valid
“1” = Logic Status/Feedback data is valid

1

Datalink Out A

“0” = Datalink Out A data is not valid
“1” = Datalink Out A data is valid

2

Datalink Out B

“0” = Datalink Out B data is not valid
“1” = Datalink Out B data is valid

3

Datalink Out C

“0” = Datalink Out C data is not valid
“1” = Datalink Out C data is valid

4

Datalink Out D

“0” = Datalink Out D data is not valid
“1” = Datalink Out D data is valid

5

Not used

Reserved for future use

6

Config Valid

“1” = The module has a valid configuration (reported on

CH1 only)

7

Config Error

“1” = The module has a configuration error (reported on

CH1 only)