Configuring the Module

3-3

* Note: Data for 16-bit Reference or 16-bit Datalinks are entered in these locations.

Idle Action / I/O Config Setting

The format for the Idle Action / I/O Config word is:

The Idle Action setting is similar to the Parameter 09 - [Idle Action 1], 26 -
[Idle Action 2]
and 43 - [Idle Action 3] settings, where:

Table 3.A Module Configuration Data Words in Controller Mode

Description

CH1 Word CH2 Word CH3 Word

Idle Action / I/O Config

0

4

8

Fault Config. Logic Command

1

5

9

Fault Config. Reference (Low) *

2

6

10

Fault Config. Reference (High)

3

7

11

Fault Config Datalink In A1 (Low) *

12

16

20

Fault Config Datalink In A1 (High)

13

17

21

Fault Config Datalink In A2 (Low) *

14

18

22

Fault Config Datalink In A2 (High)

15

19

23

Fault Config Datalink In B1 (Low) *

24

28

32

Fault Config Datalink In B1 (High)

25

29

33

Fault Config Datalink In B2 (Low) *

26

30

34

Fault Config Datalink In B2 (High)

27

31

35

Fault Config Datalink In C1 (Low) *

36

40

44

Fault Config Datalink In C1 (High)

37

41

45

Fault Config Datalink In C2 (Low) *

38

42

46

Fault Config Datalink In C2 (High)

39

43

47

Fault Config Datalink In D1 (Low) *

48

52

56

Fault Config Datalink In D1 (High)

49

53

57

Fault Config Datalink In D2 (Low) *

50

54

58

Fault Config Datalink In D2 (High)

51

55

59

Not Used

Idle Action

I/O Config

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Idle Action

Decimal

Value

Description

11

10

9

8

0

0

0

0

0

Fault - the connected drive is faulted

0

0

0

1

1

Stop - a Stop command is sent to the drive

(1)

0

0

1

0

2

Zero Data - zero's are sent to the drive

0

0

1

1

3

Hold Last - previous data continues to be sent to the drive

0

1

0

0

4

Send Fault Config - fault config data is sent to the drive

0

1

0

1

5

Invalid

0

1

1

0

6

Invalid

0

1

1

1

7

Invalid

0

0

0

0

8

Invalid

(1)

“Stop” Idle Action is not supported for SCANport connected channels. If this setting is used, the “Fault” action will
be used instead.