Module Parameters

B-7

43

[Idle Action 3]
Sets the action that the module and CH3 drive
take if the module detects that the controller was
switched to program mode. This setting is effective
only if I/O that controls the drive is transmitted
through the module.

Default:

0 = Fault

Values:

0 = Fault
1 = Stop (DPI only)
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg

Type:

Read/Write

Reset Required:

No

44

[Flt Cfg Logic 3]
Sets the Logic Command data that is sent to the
CH3 drive if Parameter 43 - [Idle Action 3] is set
to “Send Flt Cfg” and the controller is put into
Program or Test mode.

The bit definitions will depend on the drive that is
connected to the module.

Default:

0000 0000 0000 0000

Minimum:

0000 0000 0000 0000

Maximum:

1111 1111 1111 1111

Type:

Read/Write

Reset Required:

No

45

[Flt Cfg Ref 3]
Sets the Reference data that is sent to the CH3
drive if Parameter 43 - [Idle Action 3] is set to
“Send Flt Cfg” and the controller is put into
Program mode.

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read/Write

Reset Required:

No

Important: If the drive uses a 16-bit
Reference, the most significant word of this
value must be set to zero (0) or a fault will
occur.

46
47
48
49
50
51
52
53

[Flt Cfg A1 In3]
[Flt Cfg A2 In3]
[Flt Cfg B1 In3]
[Flt Cfg B2 In3]
[Flt Cfg C1 In3]
[Flt Cfg C2 In3]
[Flt Cfg D1 In3]
[Flt Cfg D2 In3]
Sets the data that is sent to the Datalink in the
CH3 drive if Parameter 43 - [Idle Action 3] is set
to “Send Flt Cfg” and the controller is put into
Program mode.

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read/Write

Reset Required:

No

Important: If the drive uses 16-bit
Datalinks, the most significant word of this
value must be set to zero (0) or a fault will
occur.

Parameter
No. Name and Description

Details

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 43 - [Idle
Action 3]
lets you determine the action of the module and connected drive if the
controller is idle. By default, this parameter faults the drive. You can set this
parameter so that the drive continues to run. Precautions should be taken to
ensure that the setting of this parameter does not create a hazard of injury or
equipment damage.

The “Stop” Idle Action is not supported for SCANport connected channels. If this
setting is used, the “Fault” action will be used instead.