Rockwell Automation 1769-SM1 Compact I/O to DPI/SCANport Module User Manual

Page 120

Advertising
background image

B-2

Module Parameters

02

[Reset Module]
No action if set to “Ready.” Resets the module if
set to “Reset Module.” Restores the module to its
factory default settings if set to “Set Defaults.” This
parameter is a command. It will be reset to “0 =
Ready” after the command has been performed.

Default:

0 = Ready

Values

0 = Ready
1 = Reset Module
2 = Set Defaults

Type:

Read/Write

Reset Required:

No

03

[Port ID 1]
Displays the port number to which CH1 is
connected.

Default:

0

Minimum:

0

Maximum:

7

Type:

Read Only

04

[Data Rate 1]
Displays the data rate used by the CH1 drive. This
data rate is set in the drive, and the module
detects it.

Default:

0 = 125 kbps

Values:

0 = 125 kbps
1 = 500 kbps

Type:

Read Only

05

[Ref/Fbk Size 1]
Displays the size of the Reference and Feedback
for the CH1 drive. The drive determines the size of
the Reference and Feedback.

Default:

0 = 16-bit

Value:

0 = 16-bit
1 = 32-bit

Type:

Read Only

06

[Datalink Size 1]
Displays the size of each Datalink word for the
CH1 drive. The drive determines the size of
Datalinks.

Default:

0 = 16-bit

Values:

0 = 16-bit
1 = 32-bit

Type:

Read Only

07

[I/O Config 1]
Sets the I/O that is transferred through the module
to the CH1 drive.

Default:

xxx0 0001

Bit Values:

0 = I/O disabled
1 = I/O enabled

Type:

Read/Write

Reset Required:

Yes

08

[I/O Actual 1]
Displays the Reference/Feedback and Datalinks
actively transmitted by the module for the CH1
drive. The value of this parameter will usually be
equal to the value of Parameter 07 - [I/O Config 1].

Default:

xxx0 0001

Bit Values:

0 = I/O disabled
1 = I/O enabled

Type:

Read Only

Parameter
No. Name and Description

Details

!

ATTENTION: Risk of injury or equipment damage exists. If the module is
transmitting I/O that controls the drive, the drive may fault when you reset the
module. Determine how your drive will respond before resetting the module.

Bit
Definition

Not Used

Not Used

Not Used

Datalink

D

Datalink

C

Datalink

B

Datalink

A

Cmd/Sts

Default

x

x

x

0

0

0

0

1

Bit

7

6

5

4

3

2

1

0

Bit
Definition

No

t Used

No

t Used

No

t Used

Dat

alink

D

Dat

alink

C

Dat

alink

B

Dat

alink

A

Cmd/Sts

Default

x

x

x

0

0

0

0

1

Bit

7

6

5

4

3

2

1

0

Advertising