Scanport pass-through fault object – Rockwell Automation 1769-SM1 Compact I/O to DPI/SCANport Module User Manual
Page 150

D-6
SCANport Objects
Instance Attributes
Common Services
SCANport Pass-Through Fault Object
(Continued)
Attribute
ID
Access
Rule
Name
Data Type
Description
0
Get
Read Fault Queue
Entry Full/All Info
STRUCT of
Fault Text
ARRAY of BYTE 16 character string (no length
information, no terminating null).
Fault Code
WORD
Fault Code
Fault Time Stamp
(1)
STRUCT
BYTE
1/100 Second (0 - 99)
BYTE
Second (0 - 59)
BYTE
Minute (0 - 59)
BYTE
Hour (0 - 23)
BYTE
Day of Week (0 - 6)
(2)
BYTE
Date (1 - 31)
BYTE
Month (1 - 12)
BYTE
Year (0 - 99)
(3)
128
Get
Fault Code and
Time Stamp
STRUCT of
Fault Code
WORD
Fault Code
Fault Time Stamp
STRUCT of
BYTE
1/100 Second (0 - 99)
BYTE
Second (0 - 59)
BYTE
Minute (0 - 59)
BYTE
Hour (0 - 23)
BYTE
BYTE
Date (1 - 31)
BYTE
Month (1 - 12)
BYTE
Year (0 - 99)
129
Get
Read Fault Text
String Only
ARRAY of BYTE 16 character string (no length
information, no terminating null).
(1)
Not available in all products.
(2)
Sunday is a value of zero.
(3)
Year is an offset from 1990.
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
Yes
Yes
Set_Attribute_Single