Module status indicator, Module status indicator -2 – Rockwell Automation 1769-SM1 Compact I/O to DPI/SCANport Module User Manual

Page 110

Advertising
background image

8-2

Troubleshooting

The MODULE status indicator is a bicolor (red and green) LED.

MODULE Status Indicator

Status

Cause

Corrective Action

Off

The 1769-SM1 module is not
powered.

Apply power to the 1769-SM1 module.

Flashing
Red

The 1769-SM1 module’s
configuration data is not valid.

• Change the controller configuration

data to valid settings.

• Reset the 1769-SM1 module

parameters to their default settings, and
then reset the 1769-SM1.

Solid Red

The 1769-SM1 module was
unable to establish
communication with the
controller.

Cycle power to the controller.

Flashing
Green

The 1769-SM1 module is
establishing communications
with the controller.

Normal behavior – no action required.

Solid Green The 1769-SM1 module has

established communications
with the controller.

Normal behavior – no action required.

Flashing
Red/Green

The 1769-SM1 module is in
boot mode.

Flash download the application code to the
1769-SM1 module.

Orange

The 1769-SM1 module is in
reset.

• Cycle power to the controller.
• Replace the 1769-SM1 module.

Advertising