Powerflex 700s drives – Rockwell Automation 1769-SM1 Compact I/O to DPI/SCANport Module User Manual
Page 160
![background image](/manuals/579881/160/background.png)
E-4
Logic Command/Status Words
Logic Status Word
PowerFlex 700S Drives
(Continued)
Logic Bits
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0 Status
Description
x Active
(1)
0 = Not Active
1 = Active
x
Running
0 = Not Running
1 = Running
x
Command
Direction
0 = Reverse
1 = Forward
x
Actual
Direction
0 = Reverse
1 = Forward
x
Accel
0 = Not Accelerating
1 = Accelerating
x
Decel
0 = Not Decelerating
1 = Decelerating
x
Jogging
0 = Not Jogging
1 = Jogging
x
Fault
0 = No Fault
1 = Fault
x
Alarm
0 = No Alarm
1 = Alarm
x
Flash Mode 0 = Not in Flash Mode
1 = In Flash Mode
x
Run Ready 0 = Not Ready to Run
1 = Ready to Run
x
At Limit
(2)
0 = Not At Limit
1 = At Limit
x
Tach Loss
Sw
0 = Not Tach Loss Sw
1 = Tach Loss Sw
x
At Zero Spd 0 = Not At Zero Speed
1 = At Zero Speed
x
At Setpt
Spd
0 = Not At Setpoint Speed
1= At Setpoint Speed
x
Enable
On
(3)
0 = Not Enabled
1 = Enable On
(1)
For PowerFlex 700S drives with Phase I Control, Logic Status bit 0 is called “Enabled.”
(2)
See parameter 304 - [Limit Status] in the PowerFlex 700S drive User Manual for a description of the limit status conditions.
(3)
This Logic Status bit is available only for PowerFlex 700S drives with Phase II Control. For drives with Phase I Control, Logic
Status bit 15 is reserved.