Powerflex 700s drives – Rockwell Automation 1769-SM1 Compact I/O to DPI/SCANport Module User Manual

Page 160

Advertising
background image

E-4

Logic Command/Status Words

Logic Status Word

PowerFlex 700S Drives

(Continued)

Logic Bits

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0 Status

Description

x Active

(1)

0 = Not Active
1 = Active

x

Running

0 = Not Running
1 = Running

x

Command
Direction

0 = Reverse
1 = Forward

x

Actual
Direction

0 = Reverse
1 = Forward

x

Accel

0 = Not Accelerating
1 = Accelerating

x

Decel

0 = Not Decelerating
1 = Decelerating

x

Jogging

0 = Not Jogging
1 = Jogging

x

Fault

0 = No Fault
1 = Fault

x

Alarm

0 = No Alarm
1 = Alarm

x

Flash Mode 0 = Not in Flash Mode

1 = In Flash Mode

x

Run Ready 0 = Not Ready to Run

1 = Ready to Run

x

At Limit

(2)

0 = Not At Limit
1 = At Limit

x

Tach Loss
Sw

0 = Not Tach Loss Sw
1 = Tach Loss Sw

x

At Zero Spd 0 = Not At Zero Speed

1 = At Zero Speed

x

At Setpt
Spd

0 = Not At Setpoint Speed
1= At Setpoint Speed

x

Enable
On

(3)

0 = Not Enabled
1 = Enable On

(1)

For PowerFlex 700S drives with Phase I Control, Logic Status bit 0 is called “Enabled.”

(2)

See parameter 304 - [Limit Status] in the PowerFlex 700S drive User Manual for a description of the limit status conditions.

(3)

This Logic Status bit is available only for PowerFlex 700S drives with Phase II Control. For drives with Phase I Control, Logic
Status bit 15 is reserved.