Configuring the Module

3-17

To set the fault configuration parameters

If you set Parameter 09 - [Idle Action 1], 26 - [Idle Action 2], or 43 -
[Idle Action 3]
to “Send Flt Cfg,” the values in the following 1769-SM1
module parameters are sent to the drive after an idle action occurs. You
must set these parameters to values required by your application.

Changes to these parameters take effect immediately. A reset is not required.

Changes to settings on some module parameters require that you reset
the 1769-SM1 module before the new settings take effect. You can reset
the module by cycling power to the module or by using Parameter 02 -
[Reset Module]
:

Set the Parameter 02 - [Reset Module] to Reset Module:

Figure 3.18 Reset Screen on an LCD HIM

When you enter 1 = Reset Module, the module will be immediately
reset. When you enter 2 = Set Defaults, the module will set all module
parameters to their factory-default settings. The value of this parameter
will be restored to 0 = Ready after the module is reset.

Parameter

Name

Description

CH1

CH2

CH3

10

27

44

Flt Cfg Logic A 16-bit value sent to the drive for Logic

Command.

11

28

45

Flt Cfg Ref

A 32-bit value (0 – 4294967295) sent to the
drive as a Reference or Datalink.

Important: If the drive uses a 16-bit
Reference or 16-bit Datalinks, the most
significant word of the value should be set to
zero (0).

12 - 19 29 - 36 46 - 53 Flt Cfg x1 In

or

Flt Cfg x2 In

Resetting the Module

!

ATTENTION: Risk of injury or equipment damage exists. If the
module is transmitting control I/O to the drive, the drive may fault when
you reset the module. Determine how your drive will respond before
resetting a connected module.

Value

Description

0

Ready (Default)

1

Reset Module

2

Set Defaults

Port 2 Device

1769-SM1

Parameter #: 02
Reset Module

1

Reset Module