Ch1 - ch3 status indicators, Ch1 - ch3 status indicators -3 – Rockwell Automation 1769-SM1 Compact I/O to DPI/SCANport Module User Manual

Page 111

Advertising
background image

Troubleshooting

8-3

The CH1, CH2, and CH3 status indicators are bicolor (red and green)
LEDs.

CH1 - CH3 Status Indicators

Status

Cause

Corrective Action

Off

The 1769-SM1 module is not
powered.

The channel is not connected
to a DPI or SCANport-
supported drive.

The port ID is not valid.

• Apply power to the 1769-SM1 module.
• Apply power to the DPI or

SCANport-supported drive.

• Connect the 1769-SM1 module to the

drive using a 1202-C* communications
cable.

Flashing
Red

An error occurred during the
initialization/logon sequence.

A ping timeout error occurred.

A status timeout error
occurred.

The channel was enabled to
pass I/O to the drive, and then
was disabled.

• Verify that the 1202-C* communications

cable is securely connected.

• Cycle power to the drive.
• Avoid disabling a channel after enabling

it to pass I/O.

Solid Red

The drive has refused an I/O
connection from the
1769-SM1 module.

Another peripheral is using
the same DPI/SCANport port
as the 1769-SM1 module.

The DPI/SCANport port
number has changed or is not
valid.

A CAN bus-off error occurred.

Important: Cycle power to the drive after
making any of the following corrections:
• Verify that all 1202-C* communications

cables are securely connected and not
damaged. Replace cables if necessary.

• Verify that the drive supports Datalinks.
• Configure the 1769-SM1 module to use

a Datalink that is not already being used
by another peripheral.

Flashing
Green

The channel is connected to a
drive, but I/O data is not being
passed between the controller
and drive.

No action required. Normal behavior if I/O
is not enabled.

Solid Green The channel is connected to a

drive, and I/O data is being
passed between the controller
and drive.

No action required.