Mounting the module, Mounting instructions, see, Panel – Rockwell Automation 1769-SM1 Compact I/O to DPI/SCANport Module User Manual

Page 24

Advertising
background image

2-4

Installing the Module

7. Attach an end cap terminator (F) to the last module in the system by

using the tongue-and-groove slots as before.

8. Lock the end cap bus terminator (G).

Important: A 1769-ECR or 1769-ECL right or left end cap must be

used to terminate the end of the serial communication
bus.

Minimum Spacing

Maintain spacing from enclosure walls, wireways, adjacent equipment,
etc. Allow 50 mm (2 in.) of space on all sides for adequate ventilation as
shown:

Allow at least 140 mm (5.5 in.) of enclosure depth to accommodate the
1769-SM1 module.

Panel Mounting

Mount the 1769-SM1 module to a panel using two screws per module.
Use M4 or #8 panhead screws. Mounting screws are required on every
module.

Mounting the Module

!

ATTENTION: Risk of equipment damage exists. During panel or
DIN rail mounting of all devices, be sure that all debris (metal chips,
wire strands, etc.) is kept from falling into the 1769-SM1 module.
Debris that falls into the module could cause damage on power up.

Compact I/O

Compact I/O

Compact I/O

Compact I/O

Compact I/O

End Cap or Cab

le

Controller

Top

Bottom

Side

Side

Advertising