Rockwell Automation 1769-SM1 Compact I/O to DPI/SCANport Module User Manual
Page 71

MicroLogix 1500 Ladder Example Program
5-17
Set Attributes Scattered Example
The Set Attributes Scattered service can be used with the DPI Parameter
object to write the value of more than one parameter with a single
message instruction.
In this example, a write of PowerFlex 70 drive parameters 140 - [Accel
Time 1], 142 - [Decel Time 1], and 100 - [Jog Speed] is being
performed.
The Message Configuration screen in RSLogix 500 for this example is
shown in
. It is assumed that the 1769-SM1 occupies slot
number 1, and that the PowerFlex 70 drive is connected to the 1769-SM1
channel 1.
for a description of the content in each
box.
Figure 5.12 Set Attributes Scattered Write Message Configuration Screen
,
for information on the
message data format.
Configuration
Value
Description
Refer to…
Service Code
Class
4C (hex)
93 (hex)
Set_Attribute_Scattered
DPI Parameter Object