Publication 2706-UM017C-EN-P - March 2006

5-4 InView Communication Module Troubleshooting

Indicators

On InView communication modules, use the COMM and Fault LED
indicators to isolate operating problems. The illustration below shows
the location of these indicators.

Communication Module Indicators

Fault LED
(LED 1)

COMM LED
(LED 2)

DF1, DH-485, DH+ LED Indications

LED

This Pattern:

Indicates:

Comm

(1)

Solid Fill

Normal operating state (no communication faults).

No Fill

Fault detected.

• Make sure controller is run mode
• Verify communication rate settings of terminal and controller
• Verify proper InView communication module board to controller connections

Flashing

When power is first applied (momentarily).

Blinking

No communications established. For DF1 terminals, the Comm indicator flashes until
an application is loaded.

Fault

No Fill

Normal operating state

Solid

Fault detected. Cycle power to the InView communication module board. If the fault
still exists, the terminal requires servicing.

Blinking

Hardware is functioning but no application is loaded or the current application is
corrupt. Reload the application into the InView communication module board.

(1)

Comm LED stays on until powerup self-tests are complete.