Application Guide 4-25
DH485 Tag Setup
• Message Trigger Address. The controller address that triggers a
message to display. This toggles between 0 and 1 in the 
controller.
• Message Data Address. The starting address of the message data
displayed. The message data contains the trigger command that 
the InView display recognizes (^T[message number]^M).
• Message Array Size. The size of the array (16 to 80 characters for
DH485) containing the message data. The maximum array size is 
dependent on the controller and must be an even integer.
• Variable Trigger Address. The controller address that triggers a
message variable to display. This toggles between 0 and 1 in the 
controller.
• Variable Data Address. The starting address of the variable data
displayed. The variable data contains the update variable 
command that the InView display recognizes (^V[variable 
data]\[variable number]^M).
IMPORTANT
All four tags for Message Trigger Address, Message 
Data Address, Variable Trigger Address, Variable 
Data Address, and the array sizes must be entered 
and established in the controller as valid tags even if 
they are not used.