3-2 InView Communication Module Connections

Cable Tables

Refer to the following tables for a summary of InView communication
module connections to controllers and network interface modules.

Runtime Communication Cables - To Processors

InView to SLC

Protocol

InView Standard Comm Port

SLC-500, 5/01,
5/02
CH1 RJ45
(DH-485)

SLC-5/03, 5/04, 5/05
CH0 (9-pin RS-232)
(DF1 or DH-485)

SLC 5/03
CH1 (RJ45)
(DH-485)

SLC 5/04
CH1
(DH+)

SLC 5/05
CH1
(ENET)

DH-485

DH-485 Communication Port (RJ45)

1747-C10
(2m/6ft)
1747-C11
(0.3m/1ft)
1747-C20
(6m/20ft)

use AIC+ Module
(1761-NET-AIC)
Connect to Port 3

1747-C10
(2m/6ft)
1747-C11
(0.3m/1ft)
1747-C20
(6m/20ft)

N/A

N/A

DeviceNet

DeviceNet Communication Port

to SLC 5/02
with 1747-SDN
and
DeviceNet cable

use 1747-SDN Module with DeviceNet cable

ControlNet

ControlNet Communication Port

N/A

not applicable - InView communication module does not support
SLC ControlNet configurations

EtherNet/IP Ethernet Comm Port

N/A

N/A

N/A

N/A

Ethernet
cable

InView to PLC-5, ControlLogix, MicroLogix1000, MicroLogix 1200, and MicroLogix 1500LSP

Protocol

InView Communication Module
Standard Comm Port

PLC-5, PLC-5C, PLC-5E
CH0 (25-pin RS-232)
(DF1)

ControlLogix
CH0 (9-pin RS-232)
(DF1)

MicroLogix 1000, 1200,
1500LSP
CH0 (8-pin Mini DIN)
(DF1 or DH-485)

DH-485

DH-485 Communication Port (RJ45)

N/A

N/A

use AIC+ Module
(1761-NET-AIC)
Connect to Port 3

DeviceNet

DeviceNet Communication Port

use 1771-SDN Module
with
DeviceNet cable

use 1756-DNB Module
with
DeviceNet cable

use 1761-NET-DNI
Module with DeviceNet
cable

ControlNet

ControlNet Communication Port

to PLC-5C
with
ControlNet cable

use 1756-CNB Module
with
ControlNet cable

N/A