Ethernet communication and tag setup screens, Ethernet communication and tag setup screens -28 – Rockwell Automation 2706-PRIO_PDH485_PDHP_PDNET_PCNET_PENET_PENET1 InView Communication Module User Manual User Manual
Page 78
 
Publication 2706-UM017C-EN-P - March 2006
4-28 Application Guide
• Message Trigger Address. The controller address that triggers a
message to display. This toggles between 0 and 1 in the 
controller.
• Message Data Address. The starting address of the message data
displayed. The message data contains the trigger command that 
the InView display recognizes (^T[message number]^M ).
• Message Array Size. The size of the array (16 to 80 characters for
DH485) containing the message data. The maximum array size is 
dependent on the controller and must be an even integer.
• Variable Trigger Address. The controller address that triggers a
message variable to display. This toggles between 0 and 1 in the 
controller.
• Variable Data Address. The starting address of the variable data
displayed. The variable data contains the update variable 
command that the InView display recognizes (^V[variable 
data]\[variable number]^M ).
• Variable Array Size. The size of the array (16 to 80 characters for
DH485) containing the variable data. The maximum array size is 
dependent on the controller and must be an even integer.
The address tags are an Integer ( N ) data file. Both the Message 
Trigger and Message Data addresses must fall entirely within a single 
80 byte block, including the Message Data array size. You can choose 
to use any Integer data file, but you cannot use more than one data 
file. For example, a Message Trigger address of N7:0 and a Message 
Data address of N9:0 is not valid. At the same time, a Message Trigger 
address of N7:0 and a Message Data address of N7:35, with a Message 
Data array size of 16, is not valid because the array falls outside of the 
40 word (80 byte ) block.
EtherNet Communication 
and Tag Setup Screens
The InView message display can communicate with the following 
controllers on an EtherNet/IP network. Be sure to set up the Ethernet 
communication module serially using a 2706-NC13 cable before 
hanging/mounting the unit. The Ethernet configuration must be set 
before it can function on the network.
• PLC-5E controller or SLC 5/05 controller
• ControlLogix controller (with 1756-ENET/B or /ENBx module)
• MicroLogix controller, FlexLogix controller, CompactLogix 
controller (with ENI module)
IMPORTANT
Variable Trigger and Variable Data addresses work 
the same as Variable Array Size.