Rockwell Automation 2706-PRIO_PDH485_PDHP_PDNET_PCNET_PENET_PENET1 InView Communication Module User Manual User Manual

Page 25

Advertising
background image

Publication 2706-UM017C-EN-P - March 2006

InView Communication Module Connections 3-3

EtherNet/IP

Ethernet Communication Port

to PLC-5E with
Ethernet cable

Use 1756-ENET Module
with Ethernet cable

Use 1761-NET-ENI
Module with Ethernet
cable

Remote I/O

Remote I/O Communication Port

shielded twinaxial cable
(1770-CD)

use 1756-DHRIO Module
with shielded twinaxial
cable (1770-CD)

N/A

DH+

DH+ Communication Port

shielded twinaxial cable
(1770-CD)

use 1756-DHRIO Module
with shielded twinaxial
cable
(1770-CD)

N/A

InView to PLC-5, ControlLogix, MicroLogix1000, MicroLogix 1200, and MicroLogix 1500LSP

Protocol

InView Communication Module
Standard Comm Port

PLC-5, PLC-5C, PLC-5E
CH0 (25-pin RS-232)
(DF1)

ControlLogix
CH0 (9-pin RS-232)
(DF1)

MicroLogix 1000, 1200,
1500LSP
CH0 (8-pin Mini DIN)
(DF1 or DH-485)

InView to MicroLogix 1500LRP, CompactLogix, and FlexLogix

Protocol

InView Communication Module
Standard Comm Port

MicroLogix 1500LRP
CH1 (9-pin RS-232)
(DF1 or DH-485)

CompactLogix CH0
(9-pin RS-232)
(DF1 or DH-485)

FlexLogix
CH0 (9-pin RS-232)
(DF1)

DH-485

DH-485 Communication Port (RJ45)

use AIC+ Module
(1761-NET-AIC)
Connect to Port 3

use AIC+ Module
(1761-NET-AIC)
Connect to Port 3

N/A

DeviceNet

DeviceNet Communication Port

use 1761-NET-DNI Module
with DeviceNet cable

N/A

ControlNet

ControlNet Communication Port

N/A

N/A

use 1788-CNC module
with ControlNet cable

EtherNet/IP Ethernet Communication Port

use 1761-NET-ENI
Module with Ethernet
cable

use 1761-NET-ENI
Module with Ethernet
cable

use 1761-NET-ENI Module
with Ethernet cable

Remote I/O

Remote I/O Communication Port

N/A

N/A

N/A

DH+

DH+ Communication Port

N/A

N/A

N/A