3-12 InView Communication Module Connections

Connect to a Single SLC Controller (Point-to-Point)

To connect a DH-485 InView communication module to a single SLC
controller use one of these cables.

• 0.3 m (1 ft) catalog no. 1747-C11
• 1.83 m (6 ft) catalog no. 1747-C10
• 6.1 m (20 ft) catalog no. 1747-C20

InView to SLC Controller Connections

The DH-485 connectors are not electrically isolated. If electrical
isolation is required, use link couplers (Catalog No. 1747-AIC).

ATTENTION

Electrical isolation using link couplers (Catalog No.
1747-AIC) is required where the distance between
the InView communication module and the SLC is
greater than 6.1 m (20 ft).

InView DH-485 Communications Port

SLC 500 Communications Connector

Cable, Catalog No. 1747-C10
Cable, Catalog No. 1747-C11
Cable, Catalog No. 1747-C20

To InView Communication

Module Terminal 8-pin

Female Plug

Connection Diagram

1
2
3
4
5
6
7
8

1
2
3
4
5
6
7
8

Connect to:

Pin #

Pin #

To SLC Communications Connector

8-pin, Male, Modular Plug

Side shown is opposite latch

Pin 1

Pin 8

Pin 1

Pin 8

SLC Controller