Publication 2706-UM017C-EN-P - March 2006

Introduction to InView Connectivity 1-5

Serial RS-485 Communications

PC based RS-485 serial networks. For multi-drop connection to an
InView display, an AIC+ (RS-232 to RS-485 converter) or a 2706-P9
type InView display can be used off the PC comm port. This allows
individual control of multiple displays on a single network up to
1219 m (4000 ft).

Set the 2706-PENET1 IP
Address

To set the 2706-PENET1 IP address:

1. Open the InView software.

2. Add a display to the project.

3. Under the display management portion of the interface, right

click the display to add and click Edit Display.

The Edit Display dialog opens.

PC

RS-232

InView Display

InView Display

RS-485

AIC+ or a
2706-P9 type
InView display

IMPORTANT

The Ethernet communications modules should be
configured serially before mounting to the InView
display or hanging/mounting the display in a high or
remote location. Communication modules require an
initial setup to establish node or IP address before
being able to function on a network. The serial
configuration requires a 2706-NC13 cable and the
InView message software.