Rockwell Automation 2706-PRIO_PDH485_PDHP_PDNET_PCNET_PENET_PENET1 InView Communication Module User Manual User Manual
Page 97
Publication 2706-UM017C-EN-P - March 2006
Application Guide 4-47
• Variable Data Address. The starting address of the variable data
displayed. The variable data contains the update variable 
command that the InView display recognizes 
(^V[variable data]\[variable number]^M).
• Variable Array Size. The size of the array (16 to 128 characters
for RIO) containing the variable data. The maximum array size is 
dependent on the controller and must be an even integer.
The address tags are either an Integer (N) or ASCII (A) data file. Both 
the Message Trigger and Message Data addresses must fall entirely 
within its designated block transfer, including the Message Data array 
size. 
Block Transfer Parameters
• Address. The starting address (in the correct controller format)
of the message data for the Block Transfer Read or Block 
Transfer Write. 
• Length. The number of words to transfer (1 to 62, or 64). The
InView display uses Length to identify the message blocks. You 
must configure 2 block transfers (only 2). The first block, labeled 
Message, contains both the Message Trigger and Data addresses. 
The second block, labeled Variable, contains the Variable Trigger 
and Variable Data addresses. Word 63 is reserved for the RIO 
Pass-through.
IMPORTANT
Variable Trigger and Variable Data addresses work 
the same as Variable Array Size.