Publication 2706-UM017C-EN-P - March 2006

3-22 InView Communication Module Connections

• Use the RS-232 port to connect an InView display to trigger

messages.

For details on connecting to the RS-232 port, see the last section in
this chapter.

InView Communication Module DeviceNet Ports

Make DeviceNet Connections

Use one of the cables below to connect the DeviceNet version of the
InView communication module to a DeviceNet network.

DeviceNet Cables

Cable

Cat. No.

DeviceNet Cable, 50 m (164 ft)

1485C-P1A50

DeviceNet Cable, 100 m (328 ft)

1485C-P1A150

DeviceNet Cable, 150 m (492 ft)

1485C-P1A300

IMPORTANT

Refer to DeviceNet Cable System Planning and
Installation manual, publication 1485-6.7.1, for
network layout and design information

Terminal Block Wiring

DeviceNet
Terminal Block

Terminal

Signal

Function

Color

1

COM

Common

Black

2

CAN_L

Signal Low

Blue

3

SHIELD

Shield

Uninsulated

4

CAN_H

Signal High

White

5

VDC+

Power Supply

Red