Publication 2706-UM017C-EN-P - March 2006

3-10 InView Communication Module Connections

Make DH+ Connections

Use the Belden 9463 twin axial cable (1770-CD) to connect a DH+
InView communication module to the DH+ link.

You can connect a DH+ link in 2 ways.

• Trunk line/drop line - from the drop line to the connector screw

terminals on the DH+ connectors of the processor.

• Daisy chain - to the connector screw terminals on the DH+

connectors on the processor.

Follow these guidelines when installing DH+ communication links.

• Do not exceed these cable lengths:

Trunk line-cable length: 3,048 m (10,000 cable ft)

Drop-cable length: 30.4 m (100 cable ft)

• Do not connect more than 64 stations on a single DH+ link

DH+ Connections

Clear 1

Shield SH

Blue 2

Blue 2

Shield SH

Clear 1

1770-CD (Belden

Cable)

PLC 5/11, -5/20, 5/26 Processor

PLC-5/30, -5/40, -5/46, -5/40L, - 5/60, -5/60C

-5/60L, -5/80, 5/80C, -5/86 Processor

InView DH+ Connector

82 or 150 Ohm Resistor