4-2 Application Guide

InView Parameters

• Node address. Node address (1 to 99 decimal) of the InView

display on the ControlNet network.

• Interscan Delay. Time interval (in ms) between display updates.

The range is 100 to 1,000 ms. The default is 100. This parameter
determines how frequently the InView display requests
unscheduled data.

Network Node Parameters

• Node Type. The type of controller that the InView display

communicates with.

• Node Address. The node address of the controller on the

ControlNet network.

For a PLC, a valid node address is 1 to 99.

ControlNet Tag Setup

IMPORTANT

All four tags for Message Trigger Address, Message
Data Address, Variable Trigger Address, Variable
Data Address, and the array sizes must be entered
and established in the controller as valid tags even if
they are not used.