Publication 2706-UM017C-EN-P - March 2006

4-10 Application Guide

PLC Processor

DeviceNet Communication Setup

InView Parameters

• Node Address. Unique address (0 to 63) of the InView display

on the DeviceNet network. You can also select 64 to use the
most recent address stored on the communications card. If you
select 64, the node address can be set from the network using a
DeviceNet network configuration tool.

• Baud Rate. Communication rate of the DeviceNet network. The

options are AutoBaud, 125 Kbps, 250 Kbps, 500 Kbps, PGM. The
default is 125 Kbps. If you select AutoBaud, the InView display
automatically detects the communication rate on startup
(provided there is sufficient network traffic). If you select PGM,
the InView display uses the most recent communication rate
stored on the communications card. PGM also allows the
communication rate to be set from the network using a
DeviceNet network configuration tool. You must reset the
display before the new communication takes effect. The
maximum cable length is restricted at higher communication
rates.