4-48 Application Guide
ControlLogix 5000 Controller
Remote I/O Communication Setup
PLC/Scanner Parameters
• Node Type. The type of controller that the InView display
communicates with.
InView Parameters
• Rack. The unique address (0 to 76 octal) of the InView display
on the remote I/O link. The options are limited to the rack
addresses supported by the type of controller selected under
PLC/Scanner.
• Baud Rate. The communication rate used on the remote I/O
link. The options are 57.6 Kbps (3,048 m (10,000 ft) max. cable
length), 115.2 Kbps (1,524 m (5,000 ft) max. cable length),
230.4 Kbps (762 m (2,500 ft) max. cable length).
• Module. The module groups used by the InView display in the
rack. Each check box represents 2 module groups. The module
groups must be contiguous.
• Chassis. Specifies whether the terminal occupies the last module
group (no higher module groups assigned) in the rack.