InView Communication Module Troubleshooting 5-5

Remote I/O LED Indications

LED

This pattern:

Indicates:

Comm

(1)

Solid Fill

Normal operating state (no communication faults)

No Fill

Communications not functioning

• Verify that communication rate and rack settings match the PLC processor

settings

• Verify proper InView communication module board to controller connections
• Verify that the PLC processor enables Remote I/O communications

Blinking

No communications established. PLC processor is in program mode.

Flashing

When power is first applied (momentarily)

Fault

No Fill

Normal operating state

Solid Fill

Fault detected. Cycle power to the terminal. If the fault still exists, the InView
communication module board requires servicing.

Blinking

Hardware is functioning but no application is loaded or the current application is
corrupt.

(1)

Comm LED stays on until powerup self-test are complete

DeviceNet, ControlNet, EtherNet/IP

LED

This Pattern:

Indicates:

Comm

Solid Fill

Normal operating state (no communication faults)

No Fill

Hardware failed

Flashing

When power is first applied (momentarily)

Blinking

No communications established

Fault

Solid Fill

Hardware failed

No Fill

Normal operating state (no communication faults)

Blinking

Hardware is functioning but no application is loaded or the current application is
corrupt