InView Communication Module Connections

Chapter Objectives

This chapter describes network and device connections for InView
communication modules.

Wire and Safety Guidelines
Cable Tables
Remote I/O Connections
DH+ Connections
DH-485 Terminal Connections
ControlNet Connections
DeviceNet Connections
EtherNet/IP Connections
Connect a Computer

Wire and Safety Guidelines

Use Electrical Safety Requirements for Employee Workplaces,
publication NFPA 70E, when you wire the InView communication
module. Also, consider these guidelines.

• Route communication cables to terminal by a separate path from

incoming power

• Where power and communication lines must cross, they should

cross at right angles. Communication lines can be installed in the
same conduit as low level DC I/O lines (less than 10 volts)

• Grounding minimizes noise from Electromagnetic Interference

(EMI) and is a safety measure in electrical installations

• Use the National Electric Code published by the National Fire

Protection Association as a source for grounding

IMPORTANT

Do not run signal wiring and power wiring
in the same conduit.

WARNING

EXPLOSION HAZARD

Do not connect or disconnect equipment unless
power has been switched off and area is known to
be non-hazardous.