InView Parameters

• InterScan Delay. Time interval (in milliseconds) between the

InView display delays before re-reading data from the logic
controller. The range is 100 to 1,000 ms. The default is 100 ms.

Network Node Parameters

• Node Type. The type of controller that the InView display

communicates with.

• Node Address. The IP address or host name of the controller on

the EtherNet/IP network that the InView display communicates.
The IP address is formatted as four sets of decimal numbers with
periods between them (10.0.0.1). The range of values for the
first set of numbers is 1 to 255, unless all fields are 0.0.0.0. The
range of values for the last three sets of decimal numbers is 0 to
255.

• Node Path. A 256-character string identifying the path to the end

node. At a minimum for a Logix controller, a valid node path is
needed to show where the processor is. Typically it is a Logix
backplane number (usually 1) followed by a space, and a Logix
slot number. Example: 1 0

EtherNet/IP Configuration