Normal operation, Error conditions – Rockwell Automation 2080-LC20-20QBBR Micro820 20-point Programmable Controllers User Manual User Manual

Page 120

Advertising
background image

Appendix B

Troubleshooting

112

Rockwell Automation Publication 2080-UM005A-EN-E - December 2013

Normal Operation

The RUN indicator is on or flashing. If a force condition is active, the FORCE
indicator turns on and remains on until all forces are removed.

Error Conditions

If an error exists within the controller, the controller indicators operate as
described in the following table.

5

SD status

Off

Uninitialized State

microSD card is not inserted.

microSD card is inserted but medium

is bad.

microSD card is inserted but file system

is bad.

Off

Error State

microSD card read/write failure.

Failure to read Configmefirst.txt in the root

directory.

Errors are detected in ConfigMeFirst.txt.

See

ConfigMeFirst.txt Errors on page 77

for

list of errors.

On

Idle State

microSD card is initialized completely
without read/write on SD card.

microSD card read/write is complete.

Blinking

Operating State

microSD card is being read/written.

6

ENET status

Steady Off

Not powered, no connection.

The device is powered off, or is powered on

but no Ethernet link established.

Flashing Green

No IP address.

The device is powered on with Ethernet link

established but no IP address is assigned yet.
Duplicate IP.

The device has detected that its IP address as

being used by another device in the network.

This status is applicable only if the device’s

duplicate IP address detection (ACD) feature

is enabled.

Steady Green

Operational.

Ethernet ink is active and the device has valid

IP address.

7

Output status

Off

Output is not energized.

On

Output is energized (logic status).

Status Indicator Description

Description

State

Indicates