Troubleshooting Appendix B

Rockwell Automation Publication 2080-UM005A-EN-E - December 2013

115

0xF005

The user program failed an integrity check while the

Micro800 controller was in Run mode.

Perform one of the following:

Cycle power on your Micro800 controller. Then, download your program
using Connected Components Workbench and start up your system.

Refer to the

Wiring Requirements and Recommendation on page 25

.

0xF006

The user program is incompatible with the Micro800

controller’s firmware revision.

Perform one of the following:

Upgrade the Micro800 controller’s firmware revision using ControlFlash.

Contact your local Rockwell Automation technical support representative
for more information about firmware revisions for your Micro800
controller. For more information on firmware revision compatibility, go to

http://www.rockwellautomation.com/support/firmware.html

0xF010

The user program contains a function/function block that

is not supported by the Micro800 controller.

Perform the following:

Modify the program so that all functions/function blocks are supported by
the Micro800 controller.

Build and download the program using Connected Components
Workbench.

Put the Micro800 controller into Run mode.

0xF014

A memory module memory error occurred.

Reprogram the memory module. If the error persists, replace the memory

module.

0xF015

An unexpected software error occurred.

Perform the following:
1. Cycle power on your Micro800 controller.
2. Build and download your program using Connected Components

Workbench, and then reinitialize any necessary data.

3. Start up your system.

Refer to the

Wire Your Controller on page 25

.

0xF016

An unexpected hardware error occurred.

Perform the following:
1. Cycle power on your Micro800 controller.
2. Build and download your program using Connected Components

Workbench, and then reinitialize any necessary data.

3. Start up your system.

Refer to the

Wire Your Controller on page 25

.

0xF017

An unexpected software error occurred due to

unexpected hardware interrupt.

If the system variable __SYSVA_USER_DATA_LOST has

been set, the controller will be able to recover the user

program, but the user data will be cleared. If not, the

Micro800 controller program will be cleared.

Perform one of the following:

Download the program using Connected Components Workbench
software.

Transfer the program using the memory module restore utility or the
microSD card.

If the fault persists, contact your local Rockwell Automation technical

support representative. For contact information, see:

http://support.rockwellautomation.com/MySupport.asp

.

0xF018

An unexpected software error occurred due to SPI

communication failure.

If the system variable __SYSVA_USER_DATA_LOST has

been set, the controller will be able to recover the user

program but the user data will be cleared. If not, the

Micro800 controller program will be cleared.

Perform one of the following:

Download the program using Connected Components Workbench
software.what

Transfer the program using the memory module restore utility or the
microSD card.

If the fault persists, contact your local Rockwell Automation technical

support representative. For contact information, see:

http://support.rockwellautomation.com/MySupport.asp

.

List of Error Codes for Micro800 Controllers

Error Code

Description

Recommended Action