Troubleshooting Appendix B

Rockwell Automation Publication 2080-UM005A-EN-E - December 2013

117

0xF050

The embedded I/O configuration in the user program is

invalid.

Perform the following:

Correct the embedded I/O configuration in the user program to match that
of the actual hardware configuration.

Build and download the program using Connected Components
Workbench.

Put the Micro800 controller into Run mode.

If the error persists, be sure to use Connected Components Workbench
programming software to develop and download the program.

For the following four error codes, z is the slot number of the plug-in module. If z = 0, then the slot number cannot be identified
0xF0Az

The plug-in I/O module experienced an error during

operation.

Perform one of the following:

Check the condition and operation of the plug-in I/O module.

Cycle power to the Micro800 controller.

If the error persists, see the Micro800 Plug-in Modules User Manual,
publication

2080-UM004

.

0xF0Bz

The plug-in I/O module configuration does not match the

actual I/O configuration detected.

Perform one of the following:

Correct the plug-in I/O module configuration in the user program to match
that of the actual hardware configuration.

Check the condition and operation of the plug-in I/O module.

Cycle power to the Micro800 controller.

Replace the plug-in I/O module.

If the error persists, see the Micro800 Plug-in Modules User Manual,
publication

2080-UM004

.

0xF0Dz

When power was applied to the plug-in I/O module or

the plug-in I/O module was removed, a hardware error

occurred.

Perform the following:

Correct the plug-in I/O module configuration in the user program.

Build and download the program using Connected Components
Workbench.

Put the Micro800 controller into Run mode.

0xF0Ez

The plug-in I/O module configuration does not match the

actual I/O configuration detected.

Perform the following:

Correct the plug-in I/O module configuration in the user program.

Build and download the program using Connected Components
Workbench.

Put the Micro800 controller into Run mode.

0xD011

The program scan time exceeded the watchdog timeout

value.

Perform one of the following:

Determine if the program is caught in a loop and correct the problem.

In the user program, increase the watchdog timeout value that is set in
the system variable _SYSVA_TCYWDG and then build and download the
program using Connected Components Workbench.

0xF850

An error occurred in the STI configuration.

Review and change the STI configuration in the Micro800 controller

properties.

List of Error Codes for Micro800 Controllers

Error Code

Description

Recommended Action